search

Products > All Products > Field mounted expansion modules

. LC-S

Picture

Light controller for analog electronic regulating ballasts

- IEX-2 bus for communication with PLC
- compatible with PC in SoftPLC applications
- analog outputs 0..10V for connecting analog ballasts
- anlog inputs for connecting potentiometers
- digital inputs
- connectors for multisensors (light, motion and IR reciver)
- easy wiring with push-wire connectors
- mounting in double ceiling, in double flour, on wall...
- 24V DC powered over IEX-2 bus

Connections

 

Technical specifications


IW (3 analog inputs)

 

 

  Range

 

0..10V (10 bit ADC, 0..1023)

  Internal pull-up

 

12V, 2mA

IX (2 digital inputs)

   

  Type

 

common-ground switch with internal
pull-up (12V DC, 1mA)

QW (4 analog outputs)

 

  Range

 

0..10V (8 bit DAC, 0..255)

  Current per channel

 

max. 10mA

  Ballasts per channel

 

max. 50

  All ballasts

 

max. 100

Connectors for sensors

 

Integra-BM multisensor

   

Integra-BM motion detector

   

Philips multisensor

Power supply

 

24V DC (18..26V DC), over IEX-2 bus

  Power consumption

 

100mA (40mA - without sensors and ballast)

Dimensions

 

108x86x45.5mm

Ordering information

ORDER CODE:
  LC-S-FB

. Print this page

Order Code


Components

Integra IQ @ Home

Documents


Product Overview


Product Catalog


Integra-BM Manual


CyBro-2 Manual


CyPro Manual


CyBro OPC Manual


Software Tools